Arizona Fire Alarm Standards

Fire Alarm Plan Review Requirements
New Plan Review Requirements
Design Criteria for 5 or fewer devices
Frequently Asked Questions Regarding Fire Alarm Requirements
Alarm Symbols

FIRE ALARM PLAN REVIEW REQUIREMENTS

Effective January 2, 2001 all requests for fire alarm permits submitted to this Jurisdiction shall comply with specific design standards. The Arizona Automatic Fire Alarm Association, Phoenix Area Valley Fire Marshals, AZ State Fire Marshals Office, and other jurisdictions have developed these standards. The intent of these standards is to provide a uniform approach for the design community. This change was made public in October of 2000.

Those items/modules checked have been adopted by this jurisdiction and shall meet standard requirements. Plan submittals that do not meet these minimum standards may be denied, or returned for corrections. Additional design standards/modules may be adopted as they are approved.

£ Base Plan package (includes 24 x 36 plans, details, specification book)

£ Standard Plan Symbols and Legend

The following are not required by Phoenix as of January 1, 2001 but may be required in the future.

Return to top of Arizona Fire Alarm Standards


New Plan Review Requirements

Adopted by the City of Phoenix – Effective January 1, 2001

In the summer of 1999 the Arizona Automatic Fire Alarm Association, Office of the State Fire Marshal, Cities of Phoenix, Scottsdale, Mesa, Glendale, Surprise Chandler, Gilbert and Central Yavapai District, formed a committee to standardize Plan Review requirements throughout the State of Arizona.

Information was requested from all of the Jurisdictions. When received the information was tabulated and compared. The common requirements were accepted and the others were discussed for clarification. Each item was discussed clarified, adopted or discarded. Some items were only required by one or two jurisdictions but they were very important to them and therefore also adopted. The list was then formulated encompassing the needs of all jurisdictions. Conflicting requirements were discussed while codes and standards were researched until agreements were reached to everyone’s satisfaction.

It is unlikely that any one jurisdiction would require all the information provided. However if we all provide the requested information then we will fulfill the needs of all jurisdictions. This will lead the way in providing the critical information needed to allow our AHJ’s to correctly evaluate each project for Fire Protection needs. Contractors will benefit from having all the information needed to install and maintain the system. Owners will get a complete design package to support their system.

Drawings

Applies to all sheets

First Sheet (Title Sheet)

If insufficient space for Wiring Legend and Symbol List on Title sheet then insert an additional sheet.

Site Plan Sheet

Floor Plan Sheets

Additional sheets as required

Riser Diagram Sheet

Details Sheet

Voltage Drop Calculations Sheets

Stand-by Battery Calculation Sheets

All of the above sheets are to be submitted as a complete set of plans for approval.
Approved plans must be kept on site during construction.

Specification Package
TABLE OF CONTENTS (each section shall have tabs and be separated accordingly. Include table of contents.)

  1. Fire Alarm Control Panels, Power Supplies and Annunciators
  2. Detection Devices
  3. Audio/Visual Devices
  4. System Components, Modules and Relays
  5. Battery Calculations and cut sheets (calcs shall also be on plans)
  6. Voltage Calculations (shall also be on plans)
  7. Compatibility Listings (matrix, table, or info showing device compatibility)
  8. Operating Instructions for entire System (This will include a copy of what will be posted adjacent to/inside FACP)
  9. Manufacturers Inspections Instructions – NFPA Chapter 7

  10. NICET Certificate (when required or if prepared by NICET)

As-Built Drawing Cabinet to be Provided

An AS BUILT Drawing Cabinet shall be installed at each project that has a new Fire Alarm System and located where acceptable to the Fire Marshal. These shall be as built drawings and shall include system modification drawings.

The cabinet shall be tampered and record a supervisory signal at the FACP

The cabinet shall contain the following:

Some of the Endorsing Agencies

Arizona Automatic Fire Alarm Association

Office of the State Fire Marshal

City of Phoenix Fire Department

City of Scottsdale Fire Department

Rural Metro Fire Department

Fountain Hills Fire Department

City of Yuma Fire Department

City of Surprise Fire Department

City of Mesa Fire Department

Central Yavapai Fire District

City of Prescott Fire Department

Sun City Fire Department

City of Kingman Fire Department

City of Tempe Fire Department

Apache Junction Fire Department

Additional information will be made available on the web at
www.azafaa.org.

Return to top of Arizona Fire Alarm Standards


Short-Format Design Criteria for 5 or fewer devices

Submit when obtaining an over-the-counter permit
Effective March 1, 2001

The following minimum criteria shall be provided on 11" x 17" or 8-1/2" x 11" sheets when obtaining an over-the-counter fire alarm permit. The number of pages is dependent only upon including the necessary information. All information shall be legible. 11" x 17" Sheets shall be folded so they can be attached to an 8-1/2" x 11" permit.

This sheet shall be submitted at the time the permit is obtained.

Return to top of Arizona Fire Alarm Standards


Common Questions To Standardized Fire Alarm Requirements

  1. What is the formal implementation date for submitting standard plans?
  2. January 1, 2001 is the formal implementation date for all standardized plan submittals. This will only apply to those jurisdictions that have adopted the standard format prior to this date. We strongly encourage use of the standard format prior to this date.

  3. Does every jurisdiction in the State require the standard format?
  4. No, not yet. As of August 2000 there are a large number of jurisdictions looking at requiring the format. We hope to include those jurisdictions that require the standard format on the web site at www.azafaa.org. Because the format is so inclusive of reviewer's needs, we do not anticipate any jurisdiction denying the standard format. Several jurisdictions outside of AZ are also looking at the format.

  5. How should the specification booklet be prepared?
  6. The fire alarm specification booklet is required to contain the following information. Each section shall be tabbed and contain the indicated information within each tab.

    1. Fire alarm control panels, power supplies and annunciators

    2. Detection/Initiation Devices (smokes, heat, pull stations, flame detection, etc)

    3. Audio/Visual devices

    4. System components, modules, relays, dialer board, etc.

    5. Battery Calculations and battery cut sheets

    6. Voltage calculations (indicate if they are included on plans)

    7. Compatibility listings (contractors responsibility to show devices are compatible)

    8. Operating instructions for entire system (this includes a copy of what will be posted adjacent to FACP)

    9. Manufacturers inspection requirements/instructions and copy of NFPA Chapter Seven information

    10. NICET or other certificates for responsible designer and lead installers as applicable

  7. How should the tabs be labeled?
  8. Our intent is that the tabs/sections be in the proper sequence. Tabs can be numbered with a front index page, or tabs may be printed with descriptions. AFAA is looking into bulk printing of pre-printed tabs.

  9. How many specification packages shall be prepared?
  10. At minimum the following will be required. One set shall be maintained at the fire alarm control panel (still being standardized), one set shall be provided to the owner prior to final inspection, and at least two sets submitted for review. The returned review sets may meet the other requirements.

  11. What type of binding should be used for the specification package?
  12. At this time the type of binding has not been standardized. This is to allow for flexibility in how the contractors present their material to the AHJ's and owners. Things to keep in mind are; will the specifications be rolled up with the plans so that they do not get lost/separated, three-ring hard binders are very hard to keep with plans, pages shall be secured to binder (not held by pressure binders).

  13. What should be printed on the outside cover of the binder?
  14. We suggest that contractors be creative and promote their companies. We request contractors indicate on the cover that the package meets the AZAFAA submittal standards. This will help AHJ's in the log-in process, and will promote to the owner that your package has been organized to a set of standards.

  15. What is the purpose of section 9, Manufacturers Inspections Instructions?
  16. This section is provided for the building owner/manager along with the field inspector and installer. It provides necessary documentation so the owner can properly maintain the system just installed. A copy of the signal codes for dialers shall also be provided. This information is required to be provided to the owner per NFPA Ch. 7.

  17. Does the AHJ keep specification packages?
  18. This will vary by the AHJ.

  19. Are specification packages required to be present for the inspection?
  20. Yes, specifications are considered part of the system design. They shall be available on site at all times, the same as the approved plans and permit.

  21. Do plans have to be submitted in the exact same format?
  22. Yes. The purpose of a standardized format is that the information is organized in such a manor that all parties will know where to look for specific information. Guidelines have been established as to what goes on each page. However, the exact layout on each of those pages could vary based on unique circumstances. All information shall be organized / grouped so that it is clear and legible.

  23. Do all the drawing sheets have to be the same size?
  24. Yes, all drawing sheets shall be the same size.

  25. Can 8-1/2" x 11" drawings be submitted?
  26. No, standard blue print size sheets shall be used. 24" x 36" is preferred.

  27. What should be in the "Scope of Work" section?
  28. This should be a brief summary of what work is taking place. (i.e. is it a new system, modification, tenant improvement, ADA upgrade, etc.) Either this section or the "Contractor Notes" section should outline who is responsible for hanging the devices, pulling wire, etc.

  29. Does the monitoring company have to be identified on the original submittal package?
  30. Yes, it is understood that the monitoring company might change once turned over to the owner. However, this is usually not the case. The approval of the monitoring company needs to be addressed during the plan review stage.

  31. Can any symbols be used to identify devices?
  32. No, a standard symbol legend has been adopted and should be used following the formal implementation date. If a standard symbol does not exist, than the designer may use their own. The main symbol legend should also identify mounting information. See web site. Simplified symbol legends may be used on floor plan sheets.

  33. Are contractors using this format currently?
  34. Yes, several contractors have started to adapt to the new format.

  35. Do I have to draw a compete set of plans for a small tenant improvement?
  36. Consult with the respective AHJ for exact requirements. We are looking at standardizing small projects at a later time.

  37. What is the cost of standardized requirements?
  38. None. You are required to prepare the plans prior to the standardization. It is felt by contractors that there will actually be a cost savings when compared to the multiple reviews and uncertainties that currently exist.

  39. Are plans required to be kept with the fire alarm panel?
  40. Yes, all new systems under this standard are required to have a plan/specification box mounted adjacent to the panel, or mounted in an accessible place with the location indicated on the panel. The box shall be keyed the same as the panel, shall be tampered, and capable of holding as-builts, specifications, instructions, maintenance history, low level passwords, software information, and a hard copy of the current program.

Return to top of Arizona Fire Alarm Standards


Alarm Symbols

For a printable list of fire alarm symbols, please click
here. (This is a pdf file, requiring Adobe Acrobat.)

Return to top of Arizona Fire Alarm Standards

Last Modified on 12/28/2001 10:58:39